Respuesta:
El módulo adicional RF-TIMBER AWC no optimiza las secciones para el estado límite de servicio o el cálculo de la resistencia al fuego. Optimization is only calculated for the ultimate limit state design.
Users must manually adjust the cross-section in RFEM or within the add-on module and can export the cross-section back into RFEM. In either scenario, the model must be rerun in order to calculate the correct internal forces with the adjusted member size.